id: "CVE-2026-63774"
page: "https://infrastack.ai/live/CVE-2026-63774"
kind: "vulnerability"
aliases: ["CVE-2026-63774"]
title: "PowerSYSTEM Center 2024 and 2026: report designer SQL injection for logged-in users"
severity: "critical"
cvss: 9.4
epss: null
exploited: false
status: "open"
category: "other"
products: [{"name": "PowerSYSTEM Center 2024", "fixed": ["2026 Update 1.1"], "affected": ">=6.0.x, <=6.2.x", "ecosystem": "vendor"}, {"name": "PowerSYSTEM Center 2026", "fixed": ["2026 Update 1.1"], "affected": ">=7.0.x, <=7.1.x", "ecosystem": "vendor"}]
ecosystems: []
tags: ["energy", "ics", "other", "powersystem-center", "reporting", "sql", "sql-injection", "subnet-solutions"]
not_affected_if: ["report-designer-disabled", "unauthenticated-only-access"]
published_at: "2026-11-06T01:17:50+00:00"
first_seen_at: "2026-11-06T01:19:01+00:00"
updated_at: "2026-11-06T01:20:15+00:00"
sources: [{"source": "nvd", "url": "https://nvd.nist.gov/vuln/detail/CVE-2026-63774", "first_seen_at": "2026-11-06T01:19:01+00:00"}, {"source": "analyst", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-307-01", "first_seen_at": "2026-11-06T01:20:15+00:00", "cites": ["https://www.cisa.gov/news-events/ics-advisories/icsa-26-307-01"]}]
exploit_sources: []
---

# PowerSYSTEM Center 2024 and 2026: report designer SQL injection for logged-in users

Link for people: https://infrastack.ai/live/CVE-2026-63774 (this .md is for agents)

SQL injection in the PowerSYSTEM Center report designer (CWE-89): insufficient input validation lets an authenticated user on an adjacent network run unauthorized SQL commands. CISA reports no known exploitation and says it is not remotely exploitable. Fix: 2026 Update 1.1.

_Summary, check and fix written by a model from the sources; labelled as such._

## Affected

- vendor:PowerSYSTEM Center 2024 affected >=6.0.x, <=6.2.x fixed 2026 Update 1.1
- vendor:PowerSYSTEM Center 2026 affected >=7.0.x, <=7.1.x fixed 2026 Update 1.1

## How to check

Check your PowerSYSTEM Center version. Affected: 2024 branch 6.0.x to 6.2.x and 2026 branch 7.0.x to 7.1.x. The 2020 branch (<=5.29.x) is not listed for this CVE (it is for the sibling CVE-2026-63017). Also check whether users can open the report designer.

## Fix

Update to PowerSYSTEM Center 2026 Update 1.1 (2024 users are told to upgrade to 2026 Update 1.1). Contact Subnet Solutions integration/support (support@subnet.com). If you cannot update, disable user access to the report designer.

## Timeline

- 2026-11-06T01:19:01+00:00 nvd https://nvd.nist.gov/vuln/detail/CVE-2026-63774
- 2026-11-06T01:20:15+00:00 analyst https://www.cisa.gov/news-events/ics-advisories/icsa-26-307-01 — Read CISA ICSA-26-307-01 (carries Subnet Solutions remediation text). No vendor-site page found; 2020 branch not affected by this CVE. Not exploited per CISA.

## Documents

- [advisory] CISA ICSA-26-307-01 Subnet Solutions PowerSYSTEM Center https://www.cisa.gov/news-events/ics-advisories/icsa-26-307-01

## From the sources

Insufficient input validation in the PowerSYSTEM Center report designer allows an authenticated user to execute unauthorized SQL commands.

---